kVA to amps calculator

Convert kVA to amps at 230 V single-phase or 400 V three-phase in seconds, in either direction. No power factor faff, no sign-up, just the number you need.

Your conversion

kVA is apparent power, so no power factor needed for this one.

Generators, transformers and supplies are rated in kVA. For real power in kW, multiply by the power factor.

Result · live
–
I = kVA × 1000 ÷ (√3 × V)
  • Supply–
Enter a value.

Guidance only. Currents are per phase for three-phase supplies. For load design, pair this with the cable size calculator and voltage drop calculator.

Free: the Electrician's Cheat Sheet Pack Printable BS 7671 quick-reference sheets: max Zs tables, cable ratings, wiring colours and more. Free, no sign-up.
How it works

How to convert kVA to amps

To convert kVA to amps, multiply the kVA by 1,000 and divide by the voltage. On a 230 V single-phase supply that's kVA × 1000 ÷ 230, about 4.3 A per kVA. On a 400 V three-phase supply it's kVA × 1000 ÷ (1.732 × 400), about 1.4 A per kVA, per phase. No power factor needed for this one.

Every generator on a hire fleet, every transformer nameplate and every supply agreement talks in kVA, but your breakers, cable tables and clamp meter all talk in amps. Getting from one to the other is a ten second job, and the reason the power factor stays out of it is that kVA is the apparent power the supply has to push out regardless of what the load does with it.

Single-phase: I = kVA × 1000 ÷ V

Three-phase: I = kVA × 1000 ÷ (1.732 × V)

The 1.732 is the square root of 3, and V is the line voltage, 400 V on a standard UK three-phase supply. So a 10 kVA load on three-phase draws 10,000 ÷ (1.732 × 400) = 14.4 A per phase, while the same 10 kVA on a 230 V single-phase supply pulls a much beefier 43.5 A down one conductor. That gap is the whole argument for putting big loads on three-phase.

Step by step

  1. Read the kVA rating off the nameplate, the hire docket or the supply agreement.
  2. Pick the supply: 230 V single-phase or 400 V three-phase. For three-phase, always use the 400 V line voltage, not 230 V.
  3. Multiply the kVA by 1,000, then divide by V for single-phase or by 1.732 × V for three-phase.
  4. Remember three-phase answers are per phase, then size the cable and protective device from that current, not from the kVA.

kVA vs kW, what's the difference?

Short version: kW = kVA × power factor. kVA is the apparent power, the total the supply must deliver. kW is the real power, the bit that actually does the work. With purely resistive loads like heaters the power factor is 1 and the two are identical. Add motors, drives and anything inductive and the kW drops below the kVA.

This is why generators and transformers are rated in kVA. The manufacturer has no idea what you are going to plug in, so they cannot know your power factor in advance. What they do know is how much current the windings can carry, and that caps the apparent power. The kVA rating is the honest one, and the real kW you get out is down to your load. If you are working the other way, from a kW load to a current, use the kW to amps calculator instead, that one has the power factor built in. For small single-phase kit rated in watts, the watts to amps calculator is quicker still.

kVA to amps at 400 V three-phase

The sizes you will meet on generators, transformers and commercial supplies. Remember these currents are per phase.

kVAAmps per phase (400 V)
5 kVA7.2 A
10 kVA14.4 A
15 kVA21.7 A
20 kVA28.9 A
30 kVA43.3 A
50 kVA72.2 A
100 kVA144.3 A
200 kVA288.7 A
500 kVA721.7 A

kVA to amps at 230 V single-phase

Smaller gennies and single-phase site supplies. Notice how quickly the current climbs, 10 kVA on single-phase is already past a 40 A breaker.

kVAAmps (230 V)
1 kVA4.3 A
2 kVA8.7 A
3 kVA13.0 A
5 kVA21.7 A
7.5 kVA32.6 A
10 kVA43.5 A

Sizing a generator from a supply current

Working backwards is just as easy, flip the formula: kVA = 1.732 × V × I ÷ 1000. Say you need to back up a 63 A three-phase supply: 1.732 × 400 × 63 ÷ 1000 = 43.6 kVA, so you would round up to the next standard set size and keep some headroom on top. Once you have the current, size the run to it with the cable size calculator.

Checking whether a supply can take the load

This conversion earns its keep the day a client asks "can our supply handle it?". On commercial sites with a half-hourly meter, the number that matters is the Maximum Import Capacity (MIC), the kVA figure agreed with the network operator. Exceed it and excess capacity charges land on the bill, so convert the site's existing demand and the proposed load into kVA before you promise anything. If the sums don't fit, the conversation moves from "new circuit" to "new connection agreement", and it's far better to have that conversation at quote stage than after the kit's been ordered.

  • A typical UK domestic single-phase supply with a 100 A cut-out is about 23 kVA. Handy for a quick sanity check on whether a load stands any chance on a domestic board.
  • Three-phase currents are per line, not totals. A 14.4 A result at 10 kVA means 14.4 A flowing in each of the three phases.
  • Sizing a genny for motor loads? Allow for starting currents of 3 to 6 times the running current. A set that idles happily at running load can stall the moment a big motor kicks in.
Quick answers

kVA to amps FAQs

How many amps is 10 kVA?

On a 230 V single-phase supply, 10 kVA is 43.5 A. On a 400 V three-phase supply it's 14.4 A per phase. Same power, wildly different current, and that's exactly why bigger loads belong on three-phase, the current gets shared across three lines instead of squeezing down one.

What is the difference between kVA and kW?

kVA is apparent power, the total the supply has to deliver. kW is real power, the part that actually does the work. They're tied together by the power factor: kW = kVA × power factor. With purely resistive loads like heaters the power factor is 1 and the two match. Add motors and drives and the kW falls below the kVA.

Why are generators rated in kVA?

Because the manufacturer doesn't know your power factor in advance. The machine is limited by the current its windings can carry, and that fixes the apparent power it can deliver, so kVA is the honest rating. What you actually get out in real kW depends entirely on what you plug into it.

What is the formula for kVA to amps three-phase?

I = kVA × 1000 ÷ (1.732 × V), where 1.732 is the square root of 3 and V is the line voltage, 400 V on a standard UK three-phase supply. So 20 kVA at 400 V is 20,000 ÷ 692.8 = 28.9 A per phase. Remember that's per phase, not a total.

Do I use 400 V or 230 V in the three-phase formula?

Use the 400 V line voltage. The 230 V figure is line to neutral, and the 1.732 in the formula already handles the relationship between the two, 230 × 1.732 is roughly 400. Feed 230 V into the three-phase formula and the current comes out far too high, which is a great way to spec a cable you didn't need.

Do I need a power factor to convert kVA to amps?

No, and that's the beauty of it. kVA is apparent power, literally volts times amps scaled up, so the power factor has already left the building. It only comes back if you want real power: kW = kVA × pf. If you're starting from a kW rating instead, use the kW to amps calculator, which has it built in.

What size generator do I need for a 63 A three-phase supply?

Flip the formula round: kVA = 1.732 × 400 × 63 ÷ 1000, which lands at about 43.6 kVA. Round up to the next standard set size and leave yourself headroom on top, especially if there are motors on the load. Starting currents of 3 to 6 times running current will flatten an undersized set.