Free electrician tool

The Electrician's Cheat Sheet Pack

Every table a working electrician actually needs, on paper, in the van. Printed from electricianseopro.co.uk/tools, where the interactive versions live.

To save: File, Print, Save as PDF.

1. Maximum Zs, MCBs and RCBOs (18th Edition, Cmin 0.95)

Values in ohms. Live version with your own readings: the Maximum Zs calculator.

RatingType BType CType D
6 A7.283.641.82
10 A4.372.191.09
16 A2.731.370.68
20 A2.191.090.55
25 A1.750.870.44
32 A1.370.680.34
40 A1.090.550.27
45 A0.970.490.24
50 A0.870.440.22
63 A0.690.350.17

On-site 80% rule: compare cold measured Zs against 0.8 × these values.

2. Voltage drop, mV/A/m (copper, 70°C thermoplastic)

Multiply by Ib and length, divide by 1000. Interactive version: the voltage drop calculator.

SizeSingle-phaseThree-phase
1.0 mm²4438.1
1.5 mm²2925.1
2.5 mm²1815.6
4 mm²119.5
6 mm²7.36.3
10 mm²4.43.8
16 mm²2.82.4
25 mm²1.751.5

Limits: 3% lighting (6.9 V at 230 V), 5% other circuits (11.5 V).

3. Twin & earth current ratings, Table 4D5 (amps)

By installation reference method. Do the full sizing job with the cable size calculator.

SizeC (clipped)100101102103A (conduit)
1.0 mm²161310.513811.5
1.5 mm²201613161014.5
2.5 mm²2721172113.520
4 mm²3727222717.526
6 mm²4734273523.532
10 mm²644536473244
16 mm²8557466342.557

4. SWA current ratings, Table 4E4A (90°C thermosetting, clipped direct, amps)

Armoured cable, clipped direct.

Size2-core3/4-core
1.5 mm²2723
2.5 mm²3631
4 mm²4942
6 mm²6253
10 mm²8573
16 mm²11094
25 mm²146124

5. Correction factors

Apply to the tabulated rating before you compare it with In.

Ambient temperature, Ca (70°C PVC)
25°C1.03
30°C1.00
35°C0.94
40°C0.87
45°C0.79
50°C0.71
Grouping, Cg (bunched)
1 circuit1.00
2 circuits0.80
3 circuits0.70
4 circuits0.65
5 circuits0.60
6 circuits0.57

6. Wiring colours

Old to new. Full detail on the UK wiring colours page.

Single-phaseOldNew
LiveRedBrown
NeutralBlackBlue
EarthGreen/YellowGreen/Yellow
Three-phaseOldNew
L1RedBrown
L2YellowBlack
L3BlueGrey
NBlackBlue

Warning: old blue = phase, new blue = neutral. Old black = neutral, new black = phase. Test everything.

7. IP ratings quick reference

First digit is solids, second is water.

First digitSolids
0None
1Objects >50 mm
2Objects >12.5 mm
3Objects >2.5 mm
4Objects >1 mm
5Dust protected
6Dust tight
Second digitWater
0None
1Vertical drips
2Drips at 15°
3Spray to 60°
4Splashes, any direction
5Water jets
6Powerful jets
7Immersion to 1 m
8Continuous immersion
9High-pressure hot jets
Common ratingTypical use
IP20Indoors
IP44Sheltered outdoor, bathroom zone 2
IP65Outdoor lighting
IP66Outdoor sockets
IP67Ground lights
IP68Submerged

8. Bathroom zones

All bathroom circuits: 30 mA RCD protection.

ZoneExtentRequirement
Zone 0Inside the bath or shower trayIPX7, SELV 12 V only
Zone 1To 2.25 m above the bath or trayIPX4 (IPX5 with water jets)
Zone 2A further 0.6 m beyond zone 1IPX4, shaver units allowed
Outside zonesRest of the roomSockets at least 3 m from the zone 1 boundary

9. Test limits

The numbers you check against on the day.

TestLimit
Insulation resistance, LV circuitsMinimum 1.0 MΩ at 500 V DC
Insulation resistance, SELV/PELVMinimum 0.5 MΩ at 250 V DC
RCD, 30 mA general typeTrip within 300 ms at rated current, 40 ms at 5×
Ring continuity (2.5/1.5 T&E)r1 ≈ rn, r2 ≈ 1.67 × r1

10. Common loads (230 V)

Quick conversions. Odd load on the job? Use the watts to amps or kW to amps calculators.

LoadPowerCurrent
Kettle3 kW13 A
Immersion heater3 kW13 A
Oven3.5 kW15.2 A
Hob7.4 kW32.2 A
Shower8.5 kW37 A
Shower9.5 kW41.3 A
Shower10.5 kW45.7 A
EV charger7.4 kW32 A

These tables are taken from the published BS 7671:2018+A2:2022 figures. Standards get amended, so verify against the current edition before relying on them for a design or a cert. Want the versions that do the maths for you? Grab the live calculators at the Helpful Tools hub.