Voltage drop calculator
Check a cable run against the BS 7671 limits in seconds. Proper mV/A/m values, the 3% and 5% limits built in, and the maximum run length at your load. Free, no sign-up.
- Voltage drop–
- mV/A/m used–
- Your limit–
- Max run at this load–
Guidance only. Values are the published BS 7671 mV/A/m figures for copper 70°C thermoplastic cables (three-phase derived at ×0.866). It assumes the conductor is at operating temperature and ignores impedance effects above 25 mm². Always verify the design against BS 7671 / the On-Site Guide.
How to calculate voltage drop (BS 7671)
What is voltage drop?
Every metre of cable has resistance, so some of your supply voltage is lost between the board and the load. A little is unavoidable. Too much and lights dim and flicker, motors run hot and die young, LED drivers reset, and the installation falls outside BS 7671. That's why every circuit design includes a voltage drop calculation, and why long runs so often end up in bigger cable than the current alone would need.
The voltage drop formula
The whole check is one line:
Voltage drop (V) = mV/A/m × design current Ib (A) × length (m) ÷ 1000
Three inputs: the cable's tabulated millivolt drop per amp per metre, the current the circuit actually carries, and the one-way route length. Multiply, divide by 1000, done. The mV/A/m value comes from the tables in Appendix 4 of BS 7671 and depends on the cable size. These are the single-phase values this calculator uses for copper 70°C thermoplastic cable:
| Cable size | mV/A/m (single-phase) | mV/A/m (three-phase) |
|---|---|---|
| 1.0 mm² | 44 | 38.1 |
| 1.5 mm² | 29 | 25.1 |
| 2.5 mm² | 18 | 15.6 |
| 4.0 mm² | 11 | 9.5 |
| 6.0 mm² | 7.3 | 6.3 |
| 10 mm² | 4.4 | 3.8 |
| 16 mm² | 2.8 | 2.4 |
| 25 mm² | 1.75 | 1.5 |
BS 7671 voltage drop limits (3% and 5%)
For an installation fed straight from the public supply, Appendix 4 recommends a maximum of 3% for lighting and 5% for everything else. On a 230 V single-phase supply that's 6.9 V and 11.5 V. On a 400 V three-phase supply it's 12 V and 20 V. Private supplies (a generator or your own transformer) get a little more headroom, 6% and 8%.
How to calculate voltage drop, step by step
- Get the design current Ib. The current the circuit actually carries, not the breaker rating. Load in kW? Convert it with the kW to amps calculator.
- Measure the route, one way. Board to the furthest point, following the actual cable path, not the crow's flight.
- Look up the mV/A/m value for your cable size in the table above (or Appendix 4 of BS 7671).
- Multiply and divide. mV/A/m × Ib × length, then divide by 1000 for volts.
- Compare against your limit. 6.9 V lighting, 11.5 V power on a 230 V supply. Or skip all five steps and type it into the calculator above.
Worked examples
Radial circuit: a 20 A radial in 2.5 mm² T&E, 18 m from the board to the last socket: 18 × 20 × 18 ÷ 1000 = 6.48 V. The power limit is 11.5 V, so it passes with room to spare. Stretch that same circuit to 35 m and you're at 12.6 V, a fail, and the reason garden office runs so often end up in 4 mm² or 6 mm².
Ring final circuit: rings get a shortcut. The current splits both ways round the ring and the worst point is the midpoint, so you divide the normal answer by 4: VD = mV/A/m × Ib × total ring length ÷ 4000. A 2.5 mm² ring with 68 m of cable carrying 26 A: 18 × 26 × 68 ÷ 4000 = 7.96 V. Pass.
Three-phase sub-main: a 60 A sub-main in 16 mm² over 40 m, using the three-phase value: 2.4 × 60 × 40 ÷ 1000 = 5.76 V against a 20 V limit. Loads of headroom, which is exactly why long outbuilding feeds love a three-phase supply.
Does temperature change the answer?
Slightly, in your favour. The tabulated mV/A/m values assume the conductor is sat at its full 70°C operating temperature. A lightly loaded cable runs cooler, has less resistance, and drops a touch less than the calculation says. There is a formal correction factor for design work, but on site the tabulated value is the safe, conservative call, if it passes on paper, it passes in copper.
- Measure the run one way, board to the furthest point. The tables already account for the return path.
- Use the design current Ib, not the breaker rating. A 32 A ring loaded to 26 A drops less than the breaker suggests.
- Voltage drop is usually what forces long runs up a size, not current-carrying capacity. Check both, the cable size calculator does them together.
Voltage drop FAQs
What are the voltage drop limits under BS 7671?
For an installation supplied directly from a public low-voltage network: 3% for lighting, 5% for other circuits. On 230 V single-phase that's 6.9 V and 11.5 V. Private supplies (generators, private transformers) get slightly more headroom, 6% and 8%.
Is the cable length one way or there and back?
One way. Measure the actual cable route from the board to the furthest point of the circuit. The mV/A/m values already include the drop on both the line and neutral conductors.
What does mV/A/m actually mean?
Millivolts dropped per amp, per metre of run. It's just resistance dressed up in convenient units: multiply by your current and length, divide by 1000, and you've got volts.
My circuit fails, what are my options?
Three realistic fixes: go up a cable size (biggest lever), shorten the route, or split the load over more circuits. For long outbuilding runs it's almost always cheaper to buy bigger cable than to dig a shorter trench.
Does grouping or ambient temperature affect voltage drop?
Not in this check, those correction factors apply to current-carrying capacity, not voltage drop. Strictly, a cooler cable drops slightly less than the tabulated value, so the standard figures err on the safe side.
How do I calculate voltage drop on a ring final circuit?
Divide by 4. The current splits both ways round the ring and the worst point is the midpoint, so the formula becomes mV/A/m × Ib × total ring length ÷ 4000. A typical 2.5 mm² ring with 68 m of cable at 26 A works out at 7.96 V, comfortably inside the 11.5 V limit.
What's the difference between single-phase and three-phase voltage drop?
Two things: the mV/A/m values are lower for three-phase (multiply the single-phase figure by 0.866), and the limits are bigger because they're percentages of 400 V, so 12 V for lighting and 20 V for power. Same formula otherwise, and this calculator handles both.