Bathroom electrical zones, explained properly
Tap a zone, get the minimum IP rating and what's actually allowed in it. Bathroom electrical zones 0, 1 and 2 under BS 7671 Section 701, sorted in seconds, no sign-up.
Pick a zone
Tap a zone to see its minimum IP rating and what's actually allowed in it.
Zone 1, above the bath or tray, up to 2.25 m
- Minimum IPIPX4 minimum (IPX5 where water jets are used for cleaning)
- AllowedShower units, extractor fans and luminaires rated for zone 1, SELV fittings. No standard 230 V accessories or socket-outlets.
Guidance only. Based on Section 701 of BS 7671. Zone boundaries move with partitions, fixed shower heads and layout quirks, measure your actual room, and when in doubt, treat it as the stricter zone.
Bathroom electrical zones under BS 7671
Section 701 of BS 7671 carves a bath or shower room into zones based on one simple question: how likely is the kit in that spot to get wet? The closer to the water, the harder the rules bite. Nail the zones and everything else, IP ratings, which fittings you can use, where the sockets go, drops into place.
| Zone | Extent | Min IP | Typical kit |
|---|---|---|---|
| Zone 0 | Interior of the bath or shower tray | IPX7 | SELV only (max 12 V AC / 30 V ripple-free DC), source outside the zones |
| Zone 1 | Directly above the bath or tray, floor to 2.25 m | IPX4 (IPX5 if water jets used for cleaning) | Shower units, zone 1 rated fans and luminaires, SELV fittings |
| Zone 2 | 0.6 m horizontally beyond zone 1, up to 2.25 m | IPX4 | Shaver supply units to BS EN 61558-2-5, zone 2 rated fittings |
| Outside zones | The rest of the room | No zonal minimum | Standard accessories, but 13 A sockets need 2.5 m clearance from zone 1 |
Zone 0: in the water
The inside of the bath or the shower tray itself. Anything here can end up submerged, so the minimum is IPX7 and the only equipment allowed is SELV at a maximum of 12 V AC or 30 V ripple-free DC, with the safety source sat outside the zones entirely. In practice that means almost nothing goes here beyond purpose-made bath lights and whirlpool kit.
Zone 1: above the bath or tray
From the rim of the bath, or the floor of the shower tray, up to 2.25 m. Minimum IPX4, rising to IPX5 where water jets are used for cleaning. Shower units live here by necessity, and fans and luminaires are fine if they're rated for zone 1. What you can't have is any standard 230 V accessory, and definitely no socket-outlets. If you're not sure what a rating on a box actually means, run it through my IP rating checker.
No tray? Wet rooms move the lines
Rip the tray out for a level-access wet room and the textbook diagram changes. With no basin to measure from, zone 1 becomes a 1.2 m horizontal radius around the fixed water outlet, still up to 2.25 m above the floor, and there is no zone 2 at all, the bigger zone 1 swallows it. If the space gets hosed down for cleaning, the minimum steps up to IPX5. Wet rooms are exactly where "measure the actual room" stops being advice and becomes the job.
Zone 2 and the socket question
Zone 2 stretches 0.6 m horizontally beyond zone 1, again up to 2.25 m. Minimum IPX4. The one accessory with a special pass is the shaver supply unit made to BS EN 61558-2-5, that's why it's the only "socket" you'll ever see next to a bathroom mirror. Standard 13 A socket-outlets must be at least 2.5 m horizontally from the zone 1 boundary, Regulation 701.512.3. You'll still hear this quoted as "the 3 m rule", that was the 17th Edition figure and it refuses to die, the 18th Edition trimmed it to 2.5 m. Either way, measure it out in a typical UK bathroom and you'll see why the honest answer to "can I have a socket in here?" is nearly always no.
RCDs and bonding
Under the 18th Edition, every circuit of a location containing a bath or shower needs 30 mA RCD additional protection. Not just the shower circuit, all of them, lighting included. Supplementary bonding can be omitted where the RCD and main bonding conditions are met, but that's an engineer's judgement, verify it on site rather than assuming. Miss it and it's exactly the sort of thing that gets coded on an inspection, see my guide to EICR codes explained for how hard.
Part P: the paperwork side
Zones decide what you can fit. Part P of the Building Regulations decides what you have to report. In England, a room containing a bath or shower is a special location, so a new circuit, a consumer unit change, or an addition or alteration within the zones is notifiable, either self-certified through a competent person scheme or run past building control before you start. Like-for-like replacements are maintenance and generally aren't. Wales has its own version of Part P and Scotland uses a different building standards system entirely, so check the rules for where the job actually is, not where you trained.
The bits that catch people out
- A fixed shower head over a bath changes the zone extents, don't assume the textbook diagram matches the room in front of you.
- A ceiling above 2.25 m technically puts fittings outside zones 1 and 2, but a steamy bathroom is still a steamy bathroom, decent IP is still the smart call. Planning the lighting layout? My downlight spacing calculator does the sums.
- Towel rails should be fed via suitably rated fused connection units sited outside the zones, not plugged into some bodged arrangement behind a panel.
Bathroom zone FAQs
Can you put a socket in a bathroom?
Almost never. Under the 18th Edition, standard 13 A socket-outlets must be at least 2.5 m horizontally from the zone 1 boundary (Regulation 701.512.3). You'll still hear it called "the 3 m rule", that was the 17th Edition figure, and most UK bathrooms don't have 2.5 m to give either. The one exception is a shaver supply unit to BS EN 61558-2-5, which is permitted in zone 2. If a customer wants a socket for hair straighteners, the honest answer is usually "not in this room".
What IP rating do I need in zone 1?
IPX4 as a minimum, which handles splashing from any direction. If water jets are used for cleaning the space, think wet rooms that get hosed down, the bar rises to IPX5. The X just means the solid-object digit isn't specified, it's the water digit doing the work here.
Can lights go directly over a shower?
Yes, and it's done every day. The fitting needs to be rated for zone 1, at least IPX4, and the circuit needs 30 mA RCD protection, which it should have anyway because every circuit of the location does. Plenty of sealed downlights are built exactly for this, just check the manufacturer states zone 1 suitability.
Do bathroom circuits need an RCD?
All of them, no exceptions. The 18th Edition requires 30 mA RCD additional protection on every circuit serving a location with a bath or shower, lighting, heating, the fan, the lot. An old install with just the shower on an RCD doesn't meet current requirements, worth flagging when you're quoting.
Where can an extractor fan go in a bathroom?
Wherever its rating allows. Plenty of fans are IPX4 and rated for zone 1, so they can sit right above the shower where they do the most good. The trap is grabbing whatever's on the van without checking, always match the fan's stated zone rating to where you're actually mounting it, and go SELV if the manufacturer requires it for that position.
Is electric underfloor heating allowed in a bathroom?
Absolutely fine with the right system. Use a mat or cable that's designed for bathrooms, install it exactly to the manufacturer's instructions, and make sure the circuit has 30 mA RCD protection like everything else in the room. Section 701 also expects the heating element to have an earthed metallic sheath, or an earthed metallic grid over it, connected to the CPC. And the MI is king here, if it says use a particular floor build-up or a specific thermostat, that's what goes in.
What if the ceiling is higher than 2.25 m, and what happened to zone 3?
Zones 1 and 2 stop at 2.25 m, so a fitting above that height sits outside the zones on paper. One catch: if a fixed shower head is mounted higher than 2.25 m, zone 1 rises with it. And outside the zones or not, the circuit still serves a bath or shower location, so 30 mA RCD protection applies, and steam doesn't read the regs, a sealed IP-rated fitting is still the smart spec over the bath. As for zone 3, it was scrapped back in the 17th Edition. Any spec that still mentions it is nearly two decades out of date.
Is bathroom electrical work notifiable under Part P?
Some of it. In England, a new circuit, a consumer unit change, or an addition or alteration within the zones of a room containing a bath or shower is notifiable, self-certify through a competent person scheme or notify building control before starting. Like-for-like replacements generally aren't. Wales and Scotland run their own rules, so check the version that applies where the job is.